Natural smoke extraction systems consist of one or more openings at the top and bottom communicating with the outside, for smoke extraction and air supply.
The total surface area of the smoke extraction sections must be greater than one hundredth of the surface area of the premises served, with a minimum of one square metre. The same applies to the air supply.
Each opening device of the smoke extraction system must be easy to operate from the floor.